Thursday, September 4, 2025

Automatic Changeover Controller (ATS) Control Card with PIC16F88 (Version 1)


🔌 Automatic Changeover Controller (Prototype V1)

1. Terminal Blocks

  • 12V DC Input Block (2 screws):

    Supplies regulated 12VDC to the circuit, typically from the GENSET battery, to power the controller.

  • AC Sensing Block (3 screws):

    Used for sensing 220V AC signals from both mains and GENSET.
    • Middle screw → Neutral line (common for both supplies).
    • Side screws → Phase line of mains and phase line of GENSET.
    • Each screw is clearly labeled on the PCB.
  • Relay Control Blocks (2 screws each):

    Connected to:
    1. Switch Relay

    2. Crank Relay

    3. Changeover Relay Driven by microcontroller GPIOs.

2. Transformers

  • Step-down Transformers (220V → 12V):

    Used to reduce mains and GENSET phase signals to a safe level for the microcontroller.


3. Rectifiers

  • Two rectifiers (1A rating):

    Each phase signal passes through a separate rectifier, converting 12VAC → 12VDC for conditioning.


4. Voltage Regulators

  • 7805 Regulators:
    Convert rectified 12VDC signals to 5VDC.

  • Signal Conditioning:
    • Each sensing line includes a 10kΩ pull-down resistor (ensures clean logic levels).
    • 470µF capacitors are used on each line for stability and noise suppression.

5. Microcontroller (PIC16F88)

The PIC16F88 monitors input signals and controls relays accordingly.

Controller Logic:

  1. Case 1 – Mains Present, GENSET Off

    → Keep all relays OFF.

  2. Case 2 – Mains Off, GENSET Off

    • Wait 30s, energize Switch Relay.
    • After 2s, energize Crank Relay for 4s.
    • Check GENSET signal for 10s.

      • If not detected, repeat crank cycle (up to 6 attempts).
    • Once GENSET detected →

      • Keep Switch Relay ON, Crank Relay OFF.
      • Energize Changeover Relay → Load shifts to GENSET.
  3. Case 3 – Mains Restored

    • Detect mains presence.
    • Wait 10s, then turn OFF Changeover Relay (load back to mains).
    • After 3s, turn OFF Switch Relay → GENSET turns off.
  4. Case 4 – Both Supplies Off

    • Retry GENSET startup process (same as Case 2).

6. Relays

  • Relay 1 – Switch Relay: Turns ON GENSET.
  • Relay 2 – Cranking Relay: Engages GENSET starter motor.
  • Relay 3 – Transfer (Changeover) Relay: Switches load between mains and GENSET.

7. Relay Driver IC

  • ULN2003:
    Acts as an interface between 5V microcontroller outputs and 12V relay coils.
    Provides current amplification and safe isolation.